Steel or PVC conduit? When to use EMT and when to use PVC

A practical comparison of steel conduit (EMT, rigid) and plastic conduit (PVC, UPVC): strength, installation, earthing, cost and where each fits.

The short answer

PVC is for concealed runs inside walls, concrete slabs and underground. Steel (EMT and rigid) is for exposed runs, impact-prone areas, factories, car parks, electrical rooms and plant rooms.

Quick comparison

ItemSteel (EMT / Rigid)Plastic (PVC / UPVC)
Impact strengthHighMedium to low
Weight and installationHeavier; needs a bender and connectorsLight; solvent-cemented, bent with a spring
FireDoes not burnSoftens with heat; standard PVC gives off smoke
Rust and moistureNeeds galvanising; rigid is better outdoorsDoes not rust; ideal for damp and underground
EarthingCan serve as an earth path when installed correctlyNeeds a separate earth wire
CostHigherLower
Typical useExposed runs, factories, car parks, electrical rooms, above false ceilingsInside concrete and walls, villas, underground (UPVC)

Types of steel conduit

EMT: thin-wall, unthreaded, joined with set-screw connectors and couplings; the most common choice for exposed runs inside buildings.

Rigid (RSC): thick-wall, threaded; for outdoor, impact-prone and hazardous areas.

Flexible: steel flex for connecting vibrating equipment such as AC units and pumps; the liquid-tight type is for damp locations.

Types of plastic conduit

Black PVC: for concealed runs in walls and ceilings, in light and heavy gauge. Heavy gauge suits concrete.

Grey UPVC (Schedule 40): stronger, for underground runs and runs between buildings.

Common mistakes

Exposed PVC in sun or impact areas that cracks over time; EMT in damp areas without watertight fittings; forgetting the earth wire in PVC runs.

The conduit type is decided by the engineer based on the project specification and the Saudi Building Code (SBC 401).

What we supply

ITCC steel conduit (EMT, rigid and flexible) with connectors, couplings and clamps, and Bahra PVC and UPVC conduit with bends, boxes and cement. Request a quote for your quantities.

References

  1. UL 797 — Electrical Metallic Tubing – Steel
  2. Steel Tube Institute — Standards for EMT (UL 797), rigid (UL 6) and IMC (UL 1242)
  3. NEMA — UL and NEC requirements for corrosion protection of galvanized steel conduit and EMT
  4. NFPA 70 — National Electrical Code