A comparison of NYA wire (British/European standard) and THHN wire (American standard): insulation, voltage, mm² vs AWG sizes, and when to use each.
The short answer
Both are single copper wires for pulling through conduit, but they belong to different systems. NYA follows British and European practice and is sized in square millimetres. THHN follows American practice and is sized in AWG. In Saudi Arabia you will find both, depending on the project specification.
Quick comparison
| Item | NYA | THHN |
|---|---|---|
| Standard | IEC 60227 / BS 6004 | UL 83 |
| Insulation | PVC | PVC with an outer nylon jacket |
| Voltage | 450/750 V | 600 V |
| Operating temperature | 70 °C | 90 °C (dry locations) |
| Sizes | mm²: 1.5, 2.5, 4, 6... | AWG: 14, 12, 10, 8... |
| Usually paired with | Metric PVC conduit | EMT in inches |
The nylon jacket on THHN makes it slicker and easier to pull through long conduit runs, and protects it from oil and abrasion.
Converting sizes between the two systems
| AWG | Area in mm² | Nearest NYA size |
|---|---|---|
| 14 | 2.08 mm² | 2.5 mm² |
| 12 | 3.31 mm² | 4 mm² |
| 10 | 5.26 mm² | 6 mm² |
| 8 | 8.37 mm² | 10 mm² |
| 6 | 13.3 mm² | 16 mm² |
The sizes do not match exactly. When switching systems, choose the equal or larger size, never the smaller one.
Stranded and flexible
NYA comes solid or stranded, and its flexible version (Flexible NYA) bends easily and is used inside panels. THHN is usually stranded from 10 AWG upwards.
Which one should I choose?
Follow the project specification and drawings. American-practice projects (EMT conduit, inch sizes) normally use THHN; British-practice projects (metric PVC conduit, IEC panels) normally use NYA. Do not mix the two systems in one circuit without the engineer’s approval.
What we supply
Standard and flexible NYA wire in several sizes, THHN wire such as 12 AWG, and green/yellow earth wire, plus Bahra PVC conduit and ITCC EMT. Request a quote for your quantities.