What do LSZH and LSOH mean on a cable, and when do you need them?

A plain guide to low smoke zero halogen (LSZH / LSOH) cables, how they differ from fire-resistant cables (MICA, FP200), and where they are required.

What LSZH and LSOH mean

LSZH stands for Low Smoke Zero Halogen and LSOH for Low Smoke Zero (0) Halogen; both mean the same thing. The sheath and insulation give off very little smoke when burned and contain no halogens (chlorine, fluorine, bromine).

Ordinary cables use PVC, which burns with thick black smoke and releases acid gas (hydrogen chloride). The smoke hides escape routes, and the gas harms lungs and corrodes electronics even after the fire is out.

According to a NIST report, the main toxic products of PVC fires are hydrogen chloride (an eye and lung irritant) and carbon monoxide. A 2020 study in the journal Materials measured the toxicity of fire effluents from PVC-insulated copper wires under different fire conditions (see references below).

PVC vs LSZH vs fire-resistant

TypeBehaviour in a fireReference standards
Standard PVCBurns with dense smoke and acid gasIEC 60227 / BS 6004
LSZH / LSOHLittle smoke, no acid gas, does not spread flameIEC 60754 (gases), IEC 61034 (smoke density), IEC 60332 (flame spread)
Fire-resistant (MICA, FP200)Keeps the circuit working during a fire for a rated time; usually LSZH as wellIEC 60331, BS 6387, BS 8434

Note: LSZH does not mean the cable keeps working in a fire. It only reduces smoke and gases. Circuits that must keep running during a fire (fire alarm, fire pumps, emergency lighting) need fire-resistant cable such as MICA or FP200.

Where LSZH is needed

Anywhere with many people and limited exits, or with valuable equipment: hospitals, schools and universities, malls, airports and stations, tunnels, data centres and server rooms, and escape routes in towers and hotels.

The project specification, the Saudi Fire Code (SBC 801) and Civil Defense requirements decide where it is mandatory. In villas, PVC cable is usually acceptable, though many owners choose LSZH for safety.

How to tell a cable is LSZH

The sheath is printed with LSZH, LSOH, LS0H or Halogen Free, along with the standard number. Sheath colour does not indicate the type; rely on the printing and the manufacturer certificate.

What we supply

We supply MICA and LSOH fire-resistant cables, Belden data cables with LSZH jackets (such as CAT6A), and power wires and cables in all common sizes. Send us your bill of quantities and we will reply with a quotation.

References

  1. IEC 60754-1 — Test on gases evolved during combustion of materials from cables (halogen acid gas content)
  2. IEC 61034-2 — Measurement of smoke density of cables burning under defined conditions
  3. NIST — Toxicity of PVC combustion products (hydrogen chloride and carbon monoxide)
  4. Kaczorek-Chrobak & Fangrat (2020), PVC-Based Copper Electric Wires under Various Fire Conditions: Toxicity of Fire Effluents, Materials 13(5):1111
  5. Dyer & Esch (1976), Polyvinyl chloride toxicity in fires: hydrogen chloride toxicity in fire fighters, JAMA 235(4)