Tables of how many wires each conduit size can take: metric PVC conduit with NYA wire, and EMT in inches with THHN wire, plus why a conduit is never filled to the top.
Why not fill the conduit to the top?
Wires in a conduit heat up under load, and the more wires there are, the harder it is for that heat to escape. Pulling through a crowded conduit also scrapes the insulation, which can cause a short circuit later.
That is why standards set a maximum fill: the American NEC allows 40% of the conduit internal area for three or more wires, and the British BS 7671 uses the cable factor / conduit factor method.
Metric PVC conduit with NYA wire (British practice)
Approximate number of stranded NYA wires for a short straight run (under 3 m, no bends):
| Conduit size | 1.5 mm² wire | 2.5 mm² wire | 4 mm² wire | 6 mm² wire |
|---|---|---|---|---|
| 16 mm | 9 | 6 | 5 | 3 |
| 20 mm | 14 | 10 | 7 | 5 |
| 25 mm | 25 | 18 | 13 | 9 |
| 32 mm | 45 | 32 | 24 | 15 |
Longer runs or runs with bends take far fewer wires (sometimes half), because pulling gets harder. Rule of thumb: the longer the run or the more bends, the bigger the conduit.
EMT in inches with THHN wire (American practice)
Maximum number of THHN wires in EMT per NEC Annex C tables:
| Conduit size | 14 AWG wire | 12 AWG wire | 10 AWG wire |
|---|---|---|---|
| 1/2 inch | 12 | 9 | 5 |
| 3/4 inch | 22 | 16 | 10 |
| 1 inch | 35 | 26 | 16 |
Site rules that matter
Do not exceed four 90-degree bends (360 degrees in total) between pull boxes; if you need more, add a pull box in between.
The more circuits share a conduit, the lower each wire’s current rating and the more derating it needs. Do not group many circuits in one conduit even if there is room.
These numbers are for estimating. Final sizing is the engineer’s, based on the drawings and the Saudi Building Code (SBC 401).