An approximate table of copper wire current ratings from 1.5 to 35 mm², how high Saudi temperatures reduce them, and common sizes for lighting, sockets and AC.
Three things decide the size
First, the current the wire will carry (the load). Second, the installation method, since a wire in conduit inside a wall cools less than an exposed one. Third, the ambient temperature and run length: heat reduces the rating and length causes voltage drop.
The basic rule: the circuit breaker rating must be less than or equal to the wire rating, so the breaker trips before the wire overheats.
Copper wire current ratings (PVC insulation, single-phase)
Reference values per IEC 60364-5-52 at 30 °C:
| Size | In conduit on a wall | Clipped direct on a wall |
|---|---|---|
| 1.5 mm² | 17.5 A | 19.5 A |
| 2.5 mm² | 24 A | 27 A |
| 4 mm² | 32 A | 36 A |
| 6 mm² | 41 A | 46 A |
| 10 mm² | 57 A | 63 A |
| 16 mm² | 76 A | 85 A |
| 25 mm² | 101 A | 112 A |
| 35 mm² | 125 A | 138 A |
Saudi heat reduces the rating
The table assumes 30 °C. On roofs, in ceiling voids and in hot rooms in Saudi Arabia, temperatures reach 45–50 °C, so multiply the rating by a correction factor (PVC insulation):
| Ambient temperature | Factor | Example: 2.5 mm² in conduit |
|---|---|---|
| 30 °C | 1.00 | 24 A |
| 40 °C | 0.87 | 21 A |
| 45 °C | 0.79 | 19 A |
| 50 °C | 0.71 | 17 A |
More circuits in the same conduit need further derating, which is why many engineers in Saudi Arabia go one size up.
Published research, including a Taif University study on how soil temperature and properties affect cable ampacity, and another study focused on regions above 50 °C in summer with dry soil, confirms that environmental conditions must be part of cable sizing (see references below).
Common sizes in villas and apartments
| Use | Common wire size | Common breaker |
|---|---|---|
| Lighting | 1.5 or 2.5 mm² | 10 or 16 A |
| General sockets | 2.5 mm² | 16 or 20 A |
| Split or window AC | 4 mm² | 20–25 A |
| Water heater and oven | 4 or 6 mm² | 25–32 A |
These are common examples for illustration only. The right size depends on the appliance rating and run length; final sizing is the engineer’s, per the Saudi Building Code (SBC 401).
Long runs
On long runs (feeding an annex, a boundary wall or a distant pump) voltage drops along the wire and equipment runs weak or overheats. The fix is a larger size even when the current rating would allow a smaller one.
What we supply
NYA and THHN wires and power cables from 1.5 mm² up to large sizes, Schneider breakers and GE disconnect switches. Send your load schedule or quantities for a quotation.
References
- IEC 60364-5-52 — Low-voltage electrical installations: wiring systems (current-carrying capacities, Annex B)
- IET — Appendix 4 of BS 7671: current-carrying capacity and rating factors
- Ghoneim, Ahmed & Sabiha (2021), Taif University: cable ampacity and temperature distribution per IEC 60287, Processes 9(3):438
- IIETA — Derating factors for underground power cables ampacity in extreme environmental conditions (summer above 50 °C)